Leak detection for critical facilities

A leak alarm is most useful when a responder can find the affected area quickly. Divide the facility into identifiable zones and choose point probes or sensing cable to suit each water path.

Bank of server racks beside an access aisle in a data centre

Equipment and data path

Where could water first appear, and which location name will send the responder to the right place?

Map water paths

Mark cooling units, drip trays, penetrations, pipework and low points. Identify access for inspection and replacement of each sensor.

Define the zones

Use a point device for a defined spot or consider cable for a longer route. Record the sensor, cable or controller limits and the facility’s interface requirements.

Route the notification

Choose the local alarm, BMS point or remote dashboard. Assign the zone name, escalation role and how disconnected sensors should be indicated.

Checks to agree before handover

  • Witness detection at a nominated point in every zone using the manufacturer’s approved test method.
  • Check that the local and remote labels match the site drawing.
  • Confirm restoration and alarm acknowledgement with the response team before handover.

Application guide published by ProSense Group.